NEC-Compliant Wire Sizing for Branch Circuits & Feeders
Voltage drop is the reduction in voltage as electrical current flows through a conductor. All wires have resistance, and this resistance causes some voltage to be "lost" as heat along the length of the wire. Too much voltage drop means equipment won't operate properly - motors run hot, lights dim, and energy is wasted.
Voltage drop occurs in both the hot and neutral conductors. For single-phase circuits, the total circuit length for calculation is 2Ã the one-way distance.
VD = Voltage Drop (volts)
K = Resistivity constant (12.9 Cu, 21.2 Al)
I = Current (amps)
L = One-way length (feet)
CM = Circular mils (wire size)
Percentage drop relative to source voltage
From service entrance to panel/MCC. Allows 3% remaining for branch circuits.
From panel to final outlet. This is the most common calculation.
Combined feeder + branch. NEC 210.19(A) & 215.2(A) Informational Notes.
Compare voltage drop across different wire sizes for your inputs:
Enter values and calculate to see comparison
Select your parameters and calculate to get a wire size recommendation.
| Drop % | Status | Action |
|---|---|---|
| †2% | Excellent | Ideal for sensitive loads |
| 2-3% | Good | Acceptable for branch circuits |
| 3-5% | Marginal | OK if feeder drop is minimal |
| > 5% | Excessive | Increase wire size or reduce length |
Motors are especially sensitive to voltage drop. A 10% drop can reduce motor torque by 19% and increase current draw, causing overheating.
Calculate the minimum wire size needed for a target voltage drop:
Find the maximum distance for a given wire size and load:
Maximum one-way distances for 3% drop with copper conductors:
| Wire Size | 120V Single Phase (feet) | 240V Single Phase (feet) | 480V Three Phase (feet) | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| 15A | 20A | 30A | 40A | 20A | 30A | 40A | 50A | 30A | 50A | 100A | |
| 14 AWG | 50 | 37 | - | - | 75 | - | - | - | - | - | - |
| 12 AWG | 79 | 59 | 40 | - | 118 | 79 | - | - | 137 | - | - |
| 10 AWG | 125 | 94 | 63 | 47 | 188 | 125 | 94 | 75 | 217 | 130 | - |
| 8 AWG | 199 | 149 | 100 | 75 | 299 | 199 | 149 | 120 | 345 | 207 | 104 |
| 6 AWG | 316 | 237 | 158 | 119 | 474 | 316 | 237 | 190 | 548 | 329 | 164 |
| 4 AWG | 503 | 377 | 251 | 188 | 754 | 503 | 377 | 302 | 871 | 523 | 261 |
| 2 AWG | 798 | 599 | 399 | 299 | 1198 | 798 | 599 | 479 | 1384 | 830 | 415 |
| 1/0 | 1267 | 950 | 634 | 475 | 1901 | 1267 | 950 | 760 | 2197 | 1318 | 659 |
| 4/0 | 2016 | 1512 | 1008 | 756 | 3024 | 2016 | 1512 | 1210 | 3494 | 2097 | 1048 |
Find your voltage and current, then read the maximum distance. If your actual distance exceeds the table value, you need a larger wire size. Dash (-) indicates wire is undersized for that current per NEC ampacity tables.
Circular mils (CM) is the cross-sectional area used in voltage drop calculations:
| AWG/kcmil | Circular Mils | Diameter (in) |
|---|---|---|
| 14 | 4,110 | 0.064 |
| 12 | 6,530 | 0.081 |
| 10 | 10,380 | 0.102 |
| 8 | 16,510 | 0.128 |
| 6 | 26,240 | 0.162 |
| 4 | 41,740 | 0.204 |
| 3 | 52,620 | 0.229 |
| 2 | 66,360 | 0.258 |
| 1 | 83,690 | 0.289 |
| 1/0 | 105,600 | 0.325 |
| 2/0 | 133,100 | 0.365 |
| 3/0 | 167,800 | 0.410 |
| 4/0 | 211,600 | 0.460 |
| 250 | 250,000 | 0.500 |
| 300 | 300,000 | 0.548 |
| 350 | 350,000 | 0.592 |
| 400 | 400,000 | 0.632 |
| 500 | 500,000 | 0.707 |
| 600 | 600,000 | 0.775 |
| 750 | 750,000 | 0.866 |
Maximum allowable current per NEC Table 310.16:
| AWG/kcmil | Copper | Aluminum |
|---|---|---|
| 14 | 20A | - |
| 12 | 25A | 20A |
| 10 | 35A | 30A |
| 8 | 50A | 45A |
| 6 | 65A | 50A |
| 4 | 85A | 65A |
| 3 | 100A | 75A |
| 2 | 115A | 90A |
| 1 | 130A | 100A |
| 1/0 | 150A | 120A |
| 2/0 | 175A | 135A |
| 3/0 | 200A | 155A |
| 4/0 | 230A | 180A |
| 250 | 255A | 205A |
| 300 | 285A | 230A |
| 350 | 310A | 250A |
| 400 | 335A | 270A |
| 500 | 380A | 310A |
Wire size must satisfy BOTH ampacity AND voltage drop requirements. Size for ampacity first, then verify voltage drop.
| Material | K Value | Notes |
|---|---|---|
| Copper (Cu) | 12.9 | Standard at 75°C |
| Aluminum (Al) | 21.2 | Standard at 75°C |
K values increase with temperature. At higher operating temperatures, resistance increases and voltage drop worsens. Values shown are for 75°C conductor temperature.
| Temp | Copper K | Aluminum K |
|---|---|---|
| 60°C | 12.2 | 20.1 |
| 75°C | 12.9 | 21.2 |
| 90°C | 13.6 | 22.4 |
Same voltage drop requires larger aluminum wire:
| Copper Size | Equivalent Aluminum | Cu Ampacity | Al Ampacity | Notes |
|---|---|---|---|---|
| 10 AWG | 8 AWG | 35A | 45A | Residential branch circuits |
| 8 AWG | 6 AWG | 50A | 50A | Subpanels, ranges |
| 6 AWG | 4 AWG | 65A | 65A | HVAC, welders |
| 4 AWG | 2 AWG | 85A | 90A | Service feeders |
| 2 AWG | 1/0 AWG | 115A | 120A | 100A services |
| 1/0 AWG | 3/0 AWG | 150A | 155A | 150A services |
| 4/0 AWG | 250 kcmil | 230A | 205A | 200A services |
| 250 kcmil | 350 kcmil | 255A | 250A | Large feeders |
| 350 kcmil | 500 kcmil | 310A | 310A | Industrial feeders |
Aluminum is typically 60-70% cheaper than copper per foot, but requires 1-2 sizes larger for equivalent voltage drop. For long runs, aluminum often provides the best value despite the larger conduit required.
100A subpanel in detached garage, 150 feet from main panel, 240V single-phase. What size copper wire is needed for 3% drop?
Given:
⢠V = 240V, 1Ï | ⢠I = 100A | ⢠L = 150 ft
⢠Max VD = 3% = 7.2V | ⢠K = 12.9 (copper)
CM = (2 Ã 12.9 Ã 100 Ã 150) / 7.2 = 53,750 CM
50 HP motor at 480V 3-phase, FLA = 65A, 400 feet from MCC. Target â€3% voltage drop with copper.
Given:
⢠V = 480V, 3Ï | ⢠I = 65A | ⢠L = 400 ft
⢠Max VD = 3% = 14.4V | ⢠K = 12.9
CM = (1.732 Ã 12.9 Ã 65 Ã 400) / 14.4 = 40,361 CM
277V lighting circuit, 20A load, 250 feet to furthest fixture. What's the voltage drop with #10 copper?
Given:
⢠V = 277V, 1Ï | ⢠I = 20A | ⢠L = 250 ft
⢠Wire = #10 AWG (10,380 CM) | ⢠K = 12.9
VD = (2 Ã 12.9 Ã 20 Ã 250) / 10,380 = 12.4V (4.5%)
200A feeder to remote building, 480V 3-phase, 500 feet. Compare copper vs aluminum for 2% max drop.
| Material | K | Required CM | Wire Size | Cost |
|---|---|---|---|---|
| Copper | 12.9 | 116,597 | 2/0 AWG | $$$$ |
| Aluminum | 21.2 | 191,594 | 4/0 AWG | $$ |
Aluminum 4/0 is approximately 50% cheaper than copper 2/0 for this run, even with larger conduit.
For copper at 3% drop:
Max feet â (CM Ã VD%) / (25.8 Ã I)
Or use: Double wire size = quadruple distance
How to verify voltage drop in the field:
Measurements must be taken under load. No-load measurements will show minimal voltage drop.
Torque varies as voltage squared. 10% drop = 19% torque loss. Motors may not start or may stall under load.
| Section | Topic | Key Point |
|---|---|---|
| 210.19(A) Note 4 | Branch Circuit VD | â€3% recommended |
| 215.2(A) Note 2 | Feeder VD | â€3% recommended |
| Combined | Total System | â€5% max |
| 310.16 | Ampacity | Conductor sizing |
| Ch.9, Table 8 | DC Resistance | Resistance values |
The 3% and 5% limits are recommendations (Informational Notes), not requirements. Many specs make them mandatory.
| â€2% | Excellent |
| â€3% | Good (branch) |
| 3-5% | Marginal |
| >5% | Excessive |
| Copper | 12.9 |
| Aluminum | 21.2 |
| 1Ï | Ã 2 |
| 3Ï | Ã â3 (1.732) |
VD = (MÃKÃIÃL) / CM
CM = (MÃKÃIÃL) / VD
L = (VDÃCM) / (MÃKÃI)