PowersYourTeam

⚡ Voltage Drop Calculator

NEC-Compliant Wire Sizing for Branch Circuits & Feeders

Overview
Calculator
Wire Sizing
Reference Tables
Examples
Field Tips
📐 What is Voltage Drop?

Voltage drop is the reduction in voltage as electrical current flows through a conductor. All wires have resistance, and this resistance causes some voltage to be "lost" as heat along the length of the wire. Too much voltage drop means equipment won't operate properly - motors run hot, lights dim, and energy is wasted.

⚠ Effects of Excessive Drop

  • Motors overheat and fail early
  • Lights flicker or dim
  • Electronics malfunction
  • Wasted energy (heat in wires)
  • Nuisance tripping

✓ NEC Recommendations

  • ≀3% for branch circuits
  • ≀5% total (feeder + branch)
  • These are recommendations, not code requirements
  • Many specs require ≀2% or ≀3% total

📋 Factors Affecting Drop

  • Wire size: Larger = less drop
  • Length: Longer = more drop
  • Current: Higher = more drop
  • Material: Copper vs aluminum
  • Temperature: Hotter = more resistance
🔌 How Voltage Drop Works
SOURCE 120V Hot conductor: -2V drop Neutral: -2V drop LOAD 116V Current Flow (I) Total Voltage Drop 4V (3.3%)

💡 Key Point

Voltage drop occurs in both the hot and neutral conductors. For single-phase circuits, the total circuit length for calculation is 2× the one-way distance.

📊 The Formula
VD = (2 × K × I × L) / CM

VD = Voltage Drop (volts)

K = Resistivity constant (12.9 Cu, 21.2 Al)

I = Current (amps)

L = One-way length (feet)

CM = Circular mils (wire size)

VD% = (VD / Vsource) × 100

Percentage drop relative to source voltage

📏 Understanding the 3% and 5% Rules
SERVICE ENTRANCE 480V FEEDER Max 2% drop (9.6V) PANEL 470.4V BRANCH CIRCUIT Max 3% drop (14.4V) LOAD 456V TOTAL DROP 24V 5% NEC Maximum

✓ Feeder: ≀2%

From service entrance to panel/MCC. Allows 3% remaining for branch circuits.

✓ Branch: ≀3%

From panel to final outlet. This is the most common calculation.

⚠ Total: ≀5%

Combined feeder + branch. NEC 210.19(A) & 215.2(A) Informational Notes.

🔢 Voltage Drop Calculator
Amperes (A)
Feet (one-way, not round trip)
📊 Wire Size Comparison

Compare voltage drop across different wire sizes for your inputs:

Enter values and calculate to see comparison

💡 Recommendation

Select your parameters and calculate to get a wire size recommendation.

📈 Voltage Profile
Calculate to see voltage profile
⚡ Quick Reference
Drop %StatusAction
≀ 2%ExcellentIdeal for sensitive loads
2-3%GoodAcceptable for branch circuits
3-5%MarginalOK if feeder drop is minimal
> 5%ExcessiveIncrease wire size or reduce length

⚠ Motor Circuits

Motors are especially sensitive to voltage drop. A 10% drop can reduce motor torque by 19% and increase current draw, causing overheating.

🔍 Find Minimum Wire Size

Calculate the minimum wire size needed for a target voltage drop:

📏 Maximum Distance Calculator

Find the maximum distance for a given wire size and load:

📋 Common Circuit Quick Reference

Maximum one-way distances for 3% drop with copper conductors:

Wire Size 120V Single Phase (feet) 240V Single Phase (feet) 480V Three Phase (feet)
15A20A30A40A 20A30A40A50A 30A50A100A
14 AWG5037--75------
12 AWG795940-11879--137--
10 AWG1259463471881259475217130-
8 AWG19914910075299199149120345207104
6 AWG316237158119474316237190548329164
4 AWG503377251188754503377302871523261
2 AWG79859939929911987985994791384830415
1/012679506344751901126795076021971318659
4/02016151210087563024201615121210349420971048

💡 Using This Table

Find your voltage and current, then read the maximum distance. If your actual distance exceeds the table value, you need a larger wire size. Dash (-) indicates wire is undersized for that current per NEC ampacity tables.

🔌 Wire Size - Circular Mils

Circular mils (CM) is the cross-sectional area used in voltage drop calculations:

AWG/kcmilCircular MilsDiameter (in)
144,1100.064
126,5300.081
1010,3800.102
816,5100.128
626,2400.162
441,7400.204
352,6200.229
266,3600.258
183,6900.289
1/0105,6000.325
2/0133,1000.365
3/0167,8000.410
4/0211,6000.460
250250,0000.500
300300,0000.548
350350,0000.592
400400,0000.632
500500,0000.707
600600,0000.775
750750,0000.866
⚡ NEC Ampacity (75°C)

Maximum allowable current per NEC Table 310.16:

AWG/kcmilCopperAluminum
1420A-
1225A20A
1035A30A
850A45A
665A50A
485A65A
3100A75A
2115A90A
1130A100A
1/0150A120A
2/0175A135A
3/0200A155A
4/0230A180A
250255A205A
300285A230A
350310A250A
400335A270A
500380A310A

⚠ Important

Wire size must satisfy BOTH ampacity AND voltage drop requirements. Size for ampacity first, then verify voltage drop.

🔧 Resistivity Constants (K)
MaterialK ValueNotes
Copper (Cu)12.9Standard at 75°C
Aluminum (Al)21.2Standard at 75°C

💡 Temperature Effect

K values increase with temperature. At higher operating temperatures, resistance increases and voltage drop worsens. Values shown are for 75°C conductor temperature.

TempCopper KAluminum K
60°C12.220.1
75°C12.921.2
90°C13.622.4
📐 Phase Multipliers
SINGLE PHASE Hot Neutral Multiplier: 2 THREE PHASE A B C Multiplier: √3 VD = 2×K×I×L / CM VD = √3×K×I×L / CM
🔄 Copper vs Aluminum Comparison

Same voltage drop requires larger aluminum wire:

Copper SizeEquivalent AluminumCu AmpacityAl AmpacityNotes
10 AWG8 AWG35A45AResidential branch circuits
8 AWG6 AWG50A50ASubpanels, ranges
6 AWG4 AWG65A65AHVAC, welders
4 AWG2 AWG85A90AService feeders
2 AWG1/0 AWG115A120A100A services
1/0 AWG3/0 AWG150A155A150A services
4/0 AWG250 kcmil230A205A200A services
250 kcmil350 kcmil255A250ALarge feeders
350 kcmil500 kcmil310A310AIndustrial feeders

💰 Cost Consideration

Aluminum is typically 60-70% cheaper than copper per foot, but requires 1-2 sizes larger for equivalent voltage drop. For long runs, aluminum often provides the best value despite the larger conduit required.

🏠 Example 1: Residential Subpanel

Scenario

100A subpanel in detached garage, 150 feet from main panel, 240V single-phase. What size copper wire is needed for 3% drop?

Given:

• V = 240V, 1φ | • I = 100A | • L = 150 ft

• Max VD = 3% = 7.2V | • K = 12.9 (copper)

CM = (2 × K × I × L) / VD

CM = (2 × 12.9 × 100 × 150) / 7.2 = 53,750 CM

Required Wire Size

2 AWG
Copper (66,360 CM) - Actual drop: 2.4%
🏭 Example 2: Industrial Motor

Scenario

50 HP motor at 480V 3-phase, FLA = 65A, 400 feet from MCC. Target ≀3% voltage drop with copper.

Given:

• V = 480V, 3φ | • I = 65A | • L = 400 ft

• Max VD = 3% = 14.4V | • K = 12.9

CM = (√3 × K × I × L) / VD

CM = (1.732 × 12.9 × 65 × 400) / 14.4 = 40,361 CM

Required Wire Size

4 AWG
Copper (41,740 CM) - VD: 2.9%, Ampacity: 85A ✓
💡 Example 3: Lighting Circuit

Scenario

277V lighting circuit, 20A load, 250 feet to furthest fixture. What's the voltage drop with #10 copper?

Given:

• V = 277V, 1φ | • I = 20A | • L = 250 ft

• Wire = #10 AWG (10,380 CM) | • K = 12.9

VD = (2 × K × I × L) / CM

VD = (2 × 12.9 × 20 × 250) / 10,380 = 12.4V (4.5%)

Voltage Drop

4.5%
⚠ Exceeds 3% - Upgrade to #8 AWG (2.8%)
🔌 Example 4: Aluminum Feeder

Scenario

200A feeder to remote building, 480V 3-phase, 500 feet. Compare copper vs aluminum for 2% max drop.

MaterialKRequired CMWire SizeCost
Copper12.9116,5972/0 AWG$$$$
Aluminum21.2191,5944/0 AWG$$

💰 Cost Analysis

Aluminum 4/0 is approximately 50% cheaper than copper 2/0 for this run, even with larger conduit.

🎯 Quick Calculation Shortcuts

🔢 The "3-4-5 Rule" (Copper, 3%, 120V)

  • #14: ~50 ft max at 15A
  • #12: ~80 ft max at 15A
  • #10: ~125 ft max at 15A
  • Double distance for 240V
  • Halve distance for double current

⚡ Quick Mental Math

For copper at 3% drop:

Max feet ≈ (CM × VD%) / (25.8 × I)

Or use: Double wire size = quadruple distance

⚠ Common Gotchas

  • Distance is ONE-WAY, not round trip
  • 3-phase uses √3 ≈ 1.732, not 2
  • Aluminum needs 1-2 sizes larger
  • Motor starting current can be 6× FLA
📏 Measuring Voltage Drop

How to verify voltage drop in the field:

  1. Measure voltage at the panel/source with load ON
  2. Measure voltage at the load/equipment with load ON
  3. Calculate: VD = Vsource - Vload
  4. Calculate %: VD% = (VD / Vsource) × 100

⚠ Important

Measurements must be taken under load. No-load measurements will show minimal voltage drop.

🔧 Troubleshooting High Drop

Common Causes

  • Loose connections: High resistance at terminations
  • Undersized wire: Original design or load increase
  • Long runs: Distance exceeds design
  • Damaged conductors: Nicks, corrosion, overheating
  • Poor splices: Wire nuts not properly tightened
  • Aluminum oxidation: Oxide layer increases resistance

✓ Solutions

  • Re-torque all connections to spec
  • Replace undersized conductors
  • Add parallel conductors
  • Move equipment closer to source
  • Use anti-oxidant on aluminum
⚡ Motor Voltage Sensitivity
MOTOR TORQUE vs VOLTAGE Voltage (%) Torque (%) 100%V = 100%T 90%V = 81%T 80%V = 64%T

⚠ Critical

Torque varies as voltage squared. 10% drop = 19% torque loss. Motors may not start or may stall under load.

📋 NEC Code References
SectionTopicKey Point
210.19(A) Note 4Branch Circuit VD≀3% recommended
215.2(A) Note 2Feeder VD≀3% recommended
CombinedTotal System≀5% max
310.16AmpacityConductor sizing
Ch.9, Table 8DC ResistanceResistance values

💡 Note

The 3% and 5% limits are recommendations (Informational Notes), not requirements. Many specs make them mandatory.

🎯 Quick Field Reference Card

Voltage Drop Limits

≀2%Excellent
≀3%Good (branch)
3-5%Marginal
>5%Excessive

K Values (75°C)

Copper12.9
Aluminum21.2

Phase Multipliers

1φ× 2
3φ× √3 (1.732)

Formulas

VD = (M×K×I×L) / CM

CM = (M×K×I×L) / VD

L = (VD×CM) / (M×K×I)