PowersYourTeam

⚡ Electrical Safety Reference

Arc Flash PPE Categories, Shock Boundaries & Safety Resources

⚠️ Important Disclaimer

This page provides general educational reference information only. Always refer to the current editions of NFPA 70E, OSHA regulations, and your site-specific electrical safety program for compliance requirements. Conduct a proper arc flash risk assessment for your specific equipment. When in doubt, consult a qualified electrical safety professional.

PPE Categories
Approach Boundaries
LOTO Procedures
Arc Flash Labels
Safety Resources
🛡️ Arc Flash PPE Categories Overview

Arc-rated (AR) PPE is categorized based on the minimum arc rating required to protect against thermal hazards from an arc flash. The arc rating indicates the level of incident energy (measured in cal/cm²) that the PPE can withstand while still providing protection against second-degree burns. Higher categories require more protection.

4
PPE Categories
1.2
cal/cm² Threshold for AR PPE
40
cal/cm² Maximum for Energized Work
>40
cal/cm² = De-energize Required
1️⃣ PPE Category 1
CAT 1
Min Arc Rating
4 cal/cm²

Required Clothing

  • Arc-rated long-sleeve shirt AND pants
  • OR Arc-rated coverall
  • Arc-rated face shield OR arc flash suit hood

Required Equipment

  • Hard hat
  • Safety glasses or goggles
  • Hearing protection (ear canal inserts)
  • Heavy-duty leather gloves
  • Leather footwear

As Needed

  • Arc-rated jacket, parka, or rainwear
  • Arc-rated hard hat liner

💡 Typical CAT 1 Tasks

Reading panel meters, IR thermography (with doors open, outside restricted boundary), operating normally enclosed energized equipment with covers on.

2️⃣ PPE Category 2
CAT 2
Min Arc Rating
8 cal/cm²

Required Clothing

  • Arc-rated long-sleeve shirt AND pants
  • OR Arc-rated coverall
  • Arc-rated flash suit hood OR arc-rated face shield WITH arc-rated balaclava

Required Equipment

  • Hard hat
  • Safety glasses or goggles
  • Hearing protection (ear canal inserts)
  • Heavy-duty leather gloves
  • Leather footwear

As Needed

  • Arc-rated jacket, parka, or rainwear
  • Arc-rated hard hat liner

💡 Typical CAT 2 Tasks

Working on energized parts (voltage testing), removing/installing CBs or starters, opening hinged covers to expose energized parts, work on control circuits with exposed parts.

3️⃣ PPE Category 3
CAT 3
Min Arc Rating
25 cal/cm²

Required Clothing (Layered System)

  • Arc-rated long-sleeve shirt (AR)
  • Arc-rated pants (AR)
  • Arc-rated coverall (AR)
  • Arc-rated flash suit jacket (AR)
  • Arc-rated flash suit pants (AR)
  • Arc-rated arc flash suit hood

Required Equipment

  • Hard hat
  • Safety glasses or goggles
  • Hearing protection (ear canal inserts)
  • Arc-rated gloves OR rubber insulating gloves with protectors
  • Leather footwear

⚠️ High-Risk Work

CAT 3 typically involves work such as inserting/removing starters from MCC buckets, racking breakers into/out of cubicles. Full arc flash suit system required.

4️⃣ PPE Category 4
CAT 4
Min Arc Rating
40 cal/cm²

Required Clothing (Full Suit System)

  • Arc-rated long-sleeve shirt (AR)
  • Arc-rated pants (AR)
  • Arc-rated coverall (AR)
  • Arc-rated arc flash suit jacket (AR)
  • Arc-rated arc flash suit pants (AR)
  • Arc-rated arc flash suit hood
  • Arc-rated gloves

Required Equipment

  • Hard hat
  • Safety glasses or goggles
  • Hearing protection (ear canal inserts)
  • Leather footwear

🚫 40 cal/cm² is the Limit

When incident energy calculations exceed 40 cal/cm², NO PPE provides adequate protection. The equipment MUST be de-energized before work can proceed. The pressure wave and blast from such an arc flash can cause severe injury regardless of thermal protection.

📋 PPE Category Quick Reference
Category Min Arc Rating Clothing Face/Head Hands Typical Tasks
CAT 1 4 cal/cm² AR shirt & pants or coverall Face shield or hood Heavy leather gloves Meter reading, IR thermography
CAT 2 8 cal/cm² AR shirt & pants or coverall Hood or face shield + balaclava Heavy leather gloves Voltage testing, CB removal
CAT 3 25 cal/cm² Multi-layer AR flash suit AR flash suit hood AR gloves or rubber + protectors MCC bucket work, racking breakers
CAT 4 40 cal/cm² Full multi-layer AR flash suit AR flash suit hood AR gloves High-energy switching operations

Important Notes

  • Arc Rating ≠ PPE Category: Your PPE's arc rating must meet or exceed the calculated incident energy OR the minimum for the category
  • Below 1.2 cal/cm²: Arc-rated PPE is not required, but non-melting clothing (cotton) should still be worn
  • Never wear meltable fabrics: Polyester, nylon, and spandex can melt and cause severe burns
  • Layering: Non-melting, flammable fiber garments may be worn under AR clothing
🎯 Electrical Safety Approach Boundaries

Approach boundaries define safe distances from exposed energized electrical conductors and circuit parts. There are two types of hazards with different boundaries: Shock Hazard Boundaries (based on voltage) and the Arc Flash Boundary (based on incident energy). Always use the GREATER of the two distances when setting up barricades.

Approach Boundaries to Exposed Energized Parts Arc Flash Boundary (1.2 cal/cm² threshold) Limited Approach Boundary Restricted Approach Boundary Exposed Energized Parts Limited (voltage-based) Restricted Unqualified OK here Qualified + PPE Required Arc Flash Boundary (variable based on incident energy) Limited Approach (shock) - voltage based Restricted Approach
Shock Protection Boundaries (AC Systems)

Based on system voltage - distances to exposed fixed circuit parts

Voltage (Phase-Phase) Limited Approach Restricted Approach
50V - 300V 3 ft 6 in (1.0 m) Avoid Contact
301V - 750V 3 ft 6 in (1.0 m) 1 ft 0 in (0.3 m)
751V - 15kV 5 ft 0 in (1.5 m) 2 ft 2 in (0.7 m)
15.1kV - 36kV 6 ft 0 in (1.8 m) 2 ft 7 in (0.8 m)
36.1kV - 46kV 8 ft 0 in (2.4 m) 2 ft 9 in (0.8 m)
46.1kV - 72.5kV 8 ft 0 in (2.4 m) 3 ft 3 in (1.0 m)

Boundary Definitions

  • Limited Approach: Distance where shock hazard exists. Unqualified persons must not enter without escort and PPE.
  • Restricted Approach: Distance where increased shock risk exists. Only qualified persons with insulating PPE may enter.
🔥 Arc Flash Boundary

The Arc Flash Boundary (AFB) is the distance from exposed energized parts where incident energy equals 1.2 cal/cm² — the threshold for onset of second-degree burns on unprotected skin.

ARC FLASH BOUNDARY DETERMINATION

The AFB is determined by:

  • Incident Energy Analysis: Calculated based on available fault current, clearing time, working distance, and equipment configuration (most accurate)
  • Arc Flash PPE Category Tables: Default boundaries provided in tables when analysis isn't available
  • Equipment Labels: Arc flash study results posted on equipment

⚠️ Key Points

  • AFB can be larger OR smaller than shock boundaries depending on incident energy
  • Use the GREATER of AFB or Limited Approach for barricade placement
  • Default AFB for low voltage (≤600V) where analysis unavailable: often 4 feet
  • Anyone crossing the AFB must wear appropriate arc-rated PPE
📐 Boundary Rules Summary

Limited Approach Boundary

  • Shock hazard exists beyond this point
  • Unqualified persons: May not enter unless escorted by qualified person AND wearing appropriate PPE
  • Qualified persons: May enter with proper training
  • Based on system voltage

Restricted Approach Boundary

  • Increased shock hazard due to arc-over potential
  • Only qualified persons may enter
  • Must use insulated tools and equipment
  • Rubber insulating gloves required
  • Energized work permit typically required

Arc Flash Boundary

  • Thermal burn hazard exists beyond this point
  • All persons must wear arc-rated PPE to enter
  • Based on incident energy (cal/cm²)
  • Determined by analysis or tables
  • Variable — can be larger or smaller than shock boundaries
🔒 Lockout/Tagout Overview

Lockout/Tagout (LOTO) procedures are required by OSHA (29 CFR 1910.147 and 1910.333) to protect workers from hazardous energy during service and maintenance. The goal is to establish an Electrically Safe Work Condition.

1910.147
Control of Hazardous Energy
1910.333
Electrical Work Practices

⚠️ Key OSHA Requirements

  • Written energy control procedures
  • Employee training (authorized, affected, other)
  • Periodic inspections of procedures
  • Standardized lockout/tagout devices
  • Exclusive control of lockout devices
📋 Six Steps of LOTO
1

Preparation

Identify all energy sources, understand equipment operation, notify affected employees, gather LOTO devices.

2

Shutdown

Shut down equipment using normal stopping procedures. Never pull disconnects under load unless rated.

3

Isolation

Operate all energy isolating devices to disconnect equipment from energy sources (disconnects, valves, etc.).

4

Lockout/Tagout

Apply locks and tags to each energy isolating device. Each authorized employee applies their own lock.

5

Stored Energy

Release, restrain, or dissipate all stored/residual energy (capacitors, springs, elevated parts, pressure, heat).

6

Verification

Verify zero energy state by attempting to operate controls and testing with appropriate meters. Test before you touch!

Establishing an Electrically Safe Work Condition

Per NFPA 70E principles, an electrically safe work condition requires verification that equipment cannot be re-energized:

📋

Identify Sources

All sources of electrical supply to equipment

🔌

Disconnect

Open disconnecting means for each source

👁️

Visual Verify

Visually verify all blades open (where possible)

🔒

Apply LOTO

Apply lockout/tagout devices

Stored Energy

Release stored electrical energy (capacitors)

🔬

Test

Test each conductor with rated meter

🌍

Ground

Apply grounding devices where required

🔬 Test Before Touch

Always use a properly rated voltage tester to verify absence of voltage. Use the Live-Dead-Live method: verify tester works on known live source, test the circuit, verify tester still works on known live source. Never assume power is off!

🏷️ Arc Flash Warning Labels

Electrical equipment must be field-marked with a label containing information to assist in determining appropriate PPE. Labels result from an arc flash risk assessment or incident energy analysis.

⚠ WARNING ARC FLASH AND SHOCK HAZARD Arc Flash Boundary: 4 ft 0 in Incident Energy: 5.2 cal/cm² @ 18 in PPE Category: CAT 2 Shock Hazard when cover removed: Limited Approach: 3 ft 6 in Restricted Approach: 1 ft 0 in Glove Class: 00 Nominal Voltage: 480V Bus ID: MCC-1A Study Date: 01/15/2025
📋 Label Information Requirements

Labels should include information to help workers select appropriate PPE:

  • Incident Energy (cal/cm²) at working distance
  • Arc Flash Boundary distance
  • PPE Category (if using table method)
  • Limited Approach Boundary for shock
  • Restricted Approach Boundary for shock
  • Glove Class required for voltage
  • Nominal System Voltage
  • Equipment Identification
  • Study Date (for incident energy method)

⚠️ Label Accuracy

Labels are based on system conditions at time of study. Changes to available fault current, protective device settings, or equipment configuration may invalidate the label. Re-evaluate after significant system changes.

🔢 Reading an Arc Flash Label

Incident Energy

Measured in cal/cm² at a specific working distance (typically 18"). This is the amount of thermal energy that would be released during an arc flash. Your PPE's arc rating must meet or exceed this value.

Working Distance

The distance from the arc source used in calculations. Typically 18 inches for low voltage equipment. Incident energy increases significantly as distance decreases — stay back when possible!

Arc Flash Boundary

Distance where incident energy drops to 1.2 cal/cm². Anyone closer must wear appropriate arc-rated PPE. Set barricades at this distance (or limited approach, whichever is greater).

PPE Category

If using the table method, the category (1-4) tells you the minimum PPE required. If incident energy is provided, select PPE with arc rating ≥ incident energy regardless of category.

🔗 Official Safety Resources & Standards

🏛️ OSHA - Electrical Safety

Federal regulations for electrical safety in the workplace. Includes 1910 Subpart S (General Industry) and 1926 Subpart K (Construction).

osha.gov/electrical →

🏛️ OSHA - Lockout/Tagout

Control of Hazardous Energy (29 CFR 1910.147). Requirements for LOTO procedures, training, and devices.

osha.gov/control-hazardous-energy →

🏛️ OSHA - Arc Flash Publication

OSHA publication on protecting employees from arc flash hazards. Free PDF download.

OSHA Publication 4472 (PDF) →

🔥 NFPA 70E

Standard for Electrical Safety in the Workplace. The primary consensus standard for arc flash and shock protection. (Purchase required)

nfpa.org/70e →

🔥 NFPA 70B

Standard for Electrical Equipment Maintenance. Now a standard (not recommended practice). Covers maintenance requirements.

nfpa.org/70b →

⚡ IEEE 1584

Guide for Performing Arc Flash Hazard Calculations. The basis for most arc flash studies and incident energy calculations.

standards.ieee.org →

⛏️ MSHA - Electrical Safety

Mine Safety and Health Administration electrical safety requirements for mining operations.

msha.gov/electrical →

🇨🇦 CSA Z462

Workplace Electrical Safety (Canadian standard). Harmonized with NFPA 70E for Canadian workplaces.

csagroup.org →

📊 NIOSH - Electrical Safety

National Institute for Occupational Safety and Health. Research and recommendations on electrical hazards.

cdc.gov/niosh →

🔌 ESFI

Electrical Safety Foundation International. Non-profit dedicated to electrical safety education and awareness.

esfi.org →

📚 Compressed Air Challenge

DOE-sponsored program for compressed air system efficiency. Free resources and training.

compressedairchallenge.org →

🏭 DOE Best Practices

Department of Energy industrial best practices for motor systems, compressed air, steam, and process heating.

energy.gov/amo →
📖 Key OSHA Regulations
Regulation Title
29 CFR 1910.147 Control of Hazardous Energy (LOTO)
29 CFR 1910.331-335 Electrical Safety-Related Work Practices
29 CFR 1910.333 Selection and Use of Work Practices
29 CFR 1910.269 Electric Power Generation, Transmission, Distribution
29 CFR 1910.132 Personal Protective Equipment (General)
29 CFR 1926.405 Electrical - Wiring Methods (Construction)
🎓 Training Requirements

Electrical safety training is required for anyone who faces a risk of electrical hazard:

Qualified Person

One who has demonstrated skills and knowledge related to construction and operation of electrical equipment and installations and has received safety training to identify and avoid hazards involved.

Unqualified Person

One with little or no training in avoiding electrical hazards. May only enter limited approach boundary when escorted by qualified person and wearing appropriate PPE.

Training Topics Should Include:

  • Skills and techniques to distinguish exposed live parts
  • Skills to determine nominal voltage
  • Approach boundary distances
  • Decision-making process for PPE selection
  • Safe use of test equipment
  • Emergency procedures (rescue, first aid, CPR)
🚨 Emergency Response

🔥 Arc Flash / Electrical Burn

  • Ensure scene is safe - de-energize if possible
  • Call 911 immediately
  • Do NOT remove adhered clothing
  • Cool burns with clean, cool water
  • Cover with sterile dressing
  • Treat for shock - keep victim warm

⚡ Electric Shock

  • Do NOT touch victim if still in contact with source
  • De-energize circuit if possible
  • Use non-conductive object to separate victim
  • Call 911
  • Check breathing and pulse
  • Begin CPR if needed and trained
  • Use AED if available

📞 Emergency Contacts

  • Emergency: 911
  • Poison Control: 1-800-222-1222
  • OSHA: 1-800-321-OSHA (6742)
  • Post site-specific emergency numbers
  • Know location of AED and first aid kit
  • Know your facility's emergency plan